Banks
own large numbers of advanced computers and other equipments, which can only be
operated in a demanding room. The room environment has a strict requirement for
the temperature, humidity, cleanness, noise, static electricity,
electromagnetic interference.
Requirements
and Challenges
1.Working
condition
24 hours consecutive stable power output at rated power
(10% overload for 1 hour permissible each 12 hours), in the following
conditions. Altitude height 1000 meters and below.
Temperature lower limit -15℃, uper limit 40℃.
2.Low
noise and clean emission
The power supply should be super low to ensure the safety
of data system; also the staff in banks can enjoy an undisturbed working
environment.
Clean emission can ensure the cleanness of the computer
room and keep the computer system and data system safe.
3.Necessarily
protective equipments
The machine can automatically inspect the start battery
voltage and give an alarm. The machine will automatically stop and give
relevant signals in the following cases: high water temperature, low water
temperature, low water level, overload, start failure. The machine will stop in
the following cases: over speed, short circuit, phase lack, over voltage,
voltage loss, low frequency. The machine will give alarm in the following
cases: low oil pressure, high water temperature, low water level, over load,
start failure, over speed, short circuit, phase lack, over voltage, voltage
loss, low frequency, low voltage for start battery, low oil level and relay
connection in the alarm system.
For auto start power generators with AMF function, ATS
helps realize auto start and auto stop. When the main fails, power generator
can start within 5 seconds (adjustable). The power generator can start of
itself consecutively for three times. The switch from main load to generator
load completes within 10 seconds and reaches rated power output in less than 12
seconds. When the mains power gets back, the generators will automatically stop
within 300 seconds (adjustable) after the machine cools Equipped with UPS.
4.With
brushless PMG AC generator, the machine have strong anti-interference
Performance, and strong short circuit withstand (usually 3
times of rated current for 10 seconds) acceptance capability