Products
CT100E3/S3

CT100E3/S3

Basic information:
Engine: 6BT5.9-G1
Alternator: UCI274C
Controller: DSE6020
Dimension and Weight:
Silent:3200×1133×1766(2059kg)
Open: 2200×830×1278(1272kg)


0.00
0.00
  
Product Description

Basic information:
Engine: 6BT5.9-G1
Alternator: UCI274C
Controller: DSE6020
Dimension and Weight:
Silent:3200×1133×1766(2059kg)
Open: 2200×830×1278(1272kg)



Engine Specifications Alternator Specification
Model 6BT5.9-G1 Model UCI274C
Manufacturer CUMMINS Frequency and Speed 50Hz/1500rpm
Number of cylinders 6 Manufacturer STAMFORD
Cylinder arrangement In-line       Prime capacity(kVA) 100
Cycle Four stroke Exciter type Brushless
Induction system Turbocharged Insulation Class H
Compression ratio 16.8:1 Protection IP23
Bore x Stroke 102 x 120 mm Rated power factor 0.8
Displacement L 5.9 Stator winding Double layer concentric
Estimated total weight (dry) kg 411 Winding pitch two thirds
Rated power KW/HP 86/115 Winding leads 12
Lubrication oil capacity L 14.2 Maximum over speed 2250Rev/min
Coolant capacity L 20.8 THF (Wave Form IEC) 2%
Governer method Mechanical TIF (Wave Form NEMA) 50
Starting system Electric Voltage regulation 1.00%
Exhaust System Lubrication system
Silence Type Industrial Total System Capacity 10.9 litre
Exhaust gas flow (max) 280 litre Normal oil pressure 207-345kPa
Exhaust gas temperature (max) 565 Normal oil temperature ≤121
Engine Electrical System Fuel system
Battery charging alternator Type of injection model WeiFu A pump
Ground (negative/positive) Negative 110% Fuel Consumption (prime) L/H 25
Starter motor rated voltage (DC) 24 V 100% Fuel Consumption (prime) L/H 22
Battery voltage 12 V 75% Fuel Consumption (prime) L/H 17.5
Volts (DC) 24 V 50% Fuel Consumption (prime) L/H 11
Cooling System
Coolant capacity (engine Only) L 9.9 Maximum coolant temperature 100
Thermostat operation range 82 - 95 Minimum Pressure Cap 69kPa
Minimum Top Tank Temperature(Prime) 100 Maximum Top Tank Temperature(Standby) 104

CT POWER Cummins series gensets have a wide power range from 22~1500KVA, which have open type, silent type, trailer type and container type which are widely used in industrial, commercial, backup, primary power source and outdoors project work and so on.