Products
CT300E3/S3

CT300E3/S3

Basic information:
Engine: NTA855-G1A
Alternator: HCI444D
Controller: DSE6020
Dimension and Weight:
Silent:4300×1483×2145(4450kg)
Open: 3000×1054×1758(2810kg)


0.00
0.00
  
Product Description

Basic information:
Engine: NTA855-G1A
Alternator: HCI444D
Controller: DSE6020
Dimension and Weight:
Silent:4300×1483×2145(4450kg)
Open: 3000×1054×1758(2810kg)



Engine Specifications Alternator Specification
Model NTA855-G1A Model HCI444D
Manufacturer CUMMINS Frequency and Speed 50Hz/1500rpm
Number of cylinders 6 Manufacturer STAMFORD
Cylinder arrangement In-line       Prime capacity(kVA) 300
Cycle Four stroke Exciter type Brushless
Induction system Turbocharged Insulation Class H
Compression ratio 14.5:1 Protection IP23
Bore x Stroke 140 X 152mm Rated power factor 0.8
Displacement L 14 Stator winding Double layer concentric
Estimated total weight (dry) kg 1410 Winding pitch two thirds
Rated power KW/HP 261/350 Winding leads 12
Lubrication oil capacity L 38.6 Maximum over speed 2250Rev/min
Coolant capacity L 50.3 THF (Wave Form IEC) 2%
Governer method Electronic TIF (Wave Form NEMA) 50
Starting system Electric Voltage regulation 1.00%
Exhaust System Lubrication system
Silence Type Industrial Total System Capacity 38litre
Exhaust gas flow (max) N/A Normal oil pressure 241-345kPa
Exhaust gas temperature (max) 470 Normal oil temperature ≤121
Engine Electrical System Fuel system
Battery charging alternator Type of injection model Direct Injection
Ground (negative/positive) Negative 110% Fuel Consumption (prime) L/H 82
Starter motor rated voltage (DC) 24 V 100% Fuel Consumption (prime) L/H 73
Battery voltage 12 V 75% Fuel Consumption (prime) L/H 55.4
Volts (DC) 24 V 50% Fuel Consumption (prime) L/H 38.2
Cooling System
Coolant capacity (engine Only) L 20.8 Maximum coolant temperature 100
Thermostat operation range 82 - 94 Minimum Pressure Cap 103kPa
Minimum Top Tank Temperature(Prime) 100 Maximum Top Tank Temperature(Standby) 104

CT POWER Cummins series gensets have a wide power range from 22~1500KVA, which have open type, silent type, trailer type and container type which are widely used in industrial, commercial, backup, primary power source and outdoors project work and so on.